Which of the below mentioned fault imposes severest duty on circuit breaker
Which of the below mentioned fault imposes severest duty on circuit breaker:
- Line to Ground fault
- Line to Line fault
- Line to Line to Line fault
- Three phase fault
Correct answer: 4. Three phase fault
Certain power system has capacitance and inductance values 0.01 µF and 1 H
Certain power system has capacitance and inductance values 0.01 µF and 1 H. The instantaneous value of current to be interrupted is 10 A. What is the value of voltage appearing across contacts of circuit breaker:
- 10 kV
- 100 kV
- 10000 kV
- None of these
Correct answer: 2. 100 kV
Explanation:
Voltage across CB, v = i√(L/C)
v = 10 √(1 / 0.01 * 10^-6) = 100000 V = 100 kV
The fuse normally protects the system against
The fuse normally protects the system against:
- Lightening surges
- Over-current
- Under-current
- Resonance
Correct answer: 2. Over-current
The making current of a circuit breaker is generally specified in terms of
The making current of a circuit breaker is generally specified in terms of:
- Peak value
- Average value
- RMS value
- None of these
Correct answer: 1. Peak value
Capacitive circuit breaking results in
Capacitive circuit breaking results in:
- Open circuit
- Short circuit
- Voltage surge
- None of these
Correct answer: 3. Voltage surge